Mounting instructions for MOSO® perforated strip type 50 E 420 as a lintel reinforcement

Please note that sand-lime bricks or other building materials, which are not named in the approvals may not be used or only with separate verification and special installation instructions!

Please contact our specialists!

MOUNTING INSTRUCTIONS

    • Roll MOSO® perforated strip off the reel and cut off with plate shears
      Cutting length = clear span of the lintel + 2 x 36 cm
    • Lay brick courses with full-mortar bedding, and install the perforated strip stays at intervals of ≤ 25 cm
    • Apply mortar for heading course generously
    • Apply MOSO® perforated strip and press into the mortar bed
    • Bend the MOSO® perforated strip stays over the MOSO® perforated strip
    • For lintels of lw ≥ 1.51 m, lay heading course and alternate insertion of a MOSO® rear anchor bracket with that of an arm above the perforated strip with a spacing of ≤ 25 in the butt joints
    • The lintel should be supported until the mortar hardens

    After completion of the brick-on-edge course the MOSO® perforated strip masonry reinforcement is placed between the stays. Then the perforated strip stays are easy to bend. Finished!

    MATERIAL REQUIREMENTS

    Material requirements per lintel *1
    Width of opening lw [m] 1.01 1.26 1.51 1.76 2.01 2.262.51
    Cutting length of perforated strip [m] 1.73 1.98 2.23 2.48 2.73 2.98 3.23
    Quantity of perforated tape stays (...) 4 5 6 7 8 9 10
    Quantity of rear anchor brackets (RVB) 6 7 8 9 10

    1 Plan for additional pinnings of brick courses on-site.
    Please note: The minimum height of masonry overlying the
    MOSO® perforated strip is 5 layers NF (≥ 42 cm).

    TECHNICAL DRAWINGS

    Fig. 4
    Fig. 5
    Fig. 6

    Please note:   

    • The use of a film (plastic sheeting) above the lintel is allowed if the embedment of the film is no more than 25 mm (for 11.5 cm facing) or 20 mm (for facing <11.5 cm) (see fig. 5).
    • Open cross joints or other openings are not permitted within the overlying masonry height of h0.
    • As an additional safeguard for brick-on-edge courses, an on-site pinning with round rods ∅ 4 mm make x 250 mm should be carried out (see fig. 6).